Effective on May 1, 2026, replacing the old GB12955‑2008 ✅

Core Change: The written Grade‑A/B/C (old Chinese naming) is officially abolished.
Tender documents, drawings and test reports shall adopt the new code: A/B/C + fire resistance duration.
(Oral reference to old grades is still acceptable.)

✅ Type A|Insulated Fire‑rated Doors (Integrity + Insulation both satisfied)
‑ A0.5 (30min) = Old Grade‑C
Only Type A corresponds to the traditional old A/B/C grades.

‑ A1.0 (60min) = Old Grade‑B (widely used for hotel guest room doors)

‑ A1.5 (90min) = Old Grade‑A (for machine rooms & fire‑compartment partitions)

Only Type A corresponds to the traditional old A/B/C grades.
✅ Type B|Partially‑insulated Fire‑rated Doors
Only 0.5‑hour insulation, longer integrity duration.
For machine rooms & shaft enclosures only. Cannot replace evacuation guest‑room doors.
✅ Type C|Non‑insulated Fire‑rated Doors
Only fire integrity guaranteed, no insulation performance.
For shaft / steel‑structure applications.
Strictly prohibited for guest‑room doors & entrance doors.
⚠️ Common Pitfall: Type‑B1.5 ≠ Old Grade‑A.
Type‑B only provides 30‑min insulation, cannot meet 90‑min insulation requirement of old Grade‑A.

📄 Tender specification template
Fire‑rated door, Model A1.0, comply with GB12955‑2024, insulated fire‑rated door, fire resistance integrity ≥60min, fire resistance insulation ≥60min.